Permit Number: T17CM04028
Parcel: 10818716A

Address:
1765 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04028
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2017 STEVE SHIELDS ZONING REVIEW Approved
05/22/2017 SSHIELD1 ENGINEERING REVIEW Passed
05/23/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide sealed and signed electrical plans per the State of Arizona requirements.
#2. The keyed notes, luminaire symbols, branch circuit, panel designations not printed on the power and lighting floorplans.
#3. Provide full compliance with the 2012 IECC for the lighting.
#4. Electrical plan review could not be completed due to lack of information.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC, 2012 IECC, City of Tucson Commercial Plan Submittal Requirements.
05/23/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a2.0; Demolition Keynotes: Please revise the note 206 (reference to a3.1).
2. Sheet a3.1; General Plan Notes: Note 18 references Sheet a8.1. Please revise the reference.
3. Sheet a8.0; Details 9 and 13: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1. Please indicate dimensions for location of the bars.
4. General: Please provide written responses to all review comments.
05/23/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/25/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
05/25/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
05/25/2017 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter for this address and the total demand served by the water meter. Provide the size of the backflow preventer.
05/26/2017 MMENDIB1 WWM REVIEW Needs Review
05/26/2017 MARTIN BROWN FIRE REVIEW Approved