Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04028
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/22/2017 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
05/23/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide sealed and signed electrical plans per the State of Arizona requirements. #2. The keyed notes, luminaire symbols, branch circuit, panel designations not printed on the power and lighting floorplans. #3. Provide full compliance with the 2012 IECC for the lighting. #4. Electrical plan review could not be completed due to lack of information. Ref: 2012 IBC sec. 107.2.1, 2011 NEC, 2012 IECC, City of Tucson Commercial Plan Submittal Requirements. |
05/23/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet a2.0; Demolition Keynotes: Please revise the note 206 (reference to a3.1). 2. Sheet a3.1; General Plan Notes: Note 18 references Sheet a8.1. Please revise the reference. 3. Sheet a8.0; Details 9 and 13: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1. Please indicate dimensions for location of the bars. 4. General: Please provide written responses to all review comments. |
05/23/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/25/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
05/25/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/25/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter for this address and the total demand served by the water meter. Provide the size of the backflow preventer. |
05/26/2017 | MMENDIB1 | WWM | REVIEW | Needs Review | |
05/26/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |