Permit Number: T17CM03990
Parcel: 12602006A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03990
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Reprint the drawing for legibility (including the registrant's seal).
2. Provide ventilation for the repair area (0.75 CFM/SF)
05/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/19/2017 ROBERT SHERRY WATER REVIEW Completed
05/19/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change The occupant load for the repair area should be recalculated. A 500 SF/occupant was used, and should be revised to 100 SF/occupant. Please revise.
05/24/2017 KROBLES1 ENGINEERING REVIEW Needs Review
05/24/2017 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/24/2017 KROBLES1 FIRE REVIEW Needs Review
05/24/2017 KROBLES1 ZONING REVIEW Needs Review