Permit Number: T17CM03983
Parcel: 133400020

Address:
555 N PANTANO RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM03983
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrcal plan review comments. Also provide a written response. Ref: Plan sheet E2,. (a) The gronding electrode conductor shown on the grounding detail is undersized. Should be a 3/0 cu minimum, per NEC art 250.66.
(b) It is unusual not to have a neutral conductor for the existing distribution panel feeders shown as (two wire) 480 volt feeders for the distribution panels, but not a code violation. Please verify a neutral conductor is not needed.
Ref: 2012 IBC 107.2.1, 2011 NEC
06/05/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved