Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM03983
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrcal plan review comments. Also provide a written response. Ref: Plan sheet E2,. (a) The gronding electrode conductor shown on the grounding detail is undersized. Should be a 3/0 cu minimum, per NEC art 250.66. (b) It is unusual not to have a neutral conductor for the existing distribution panel feeders shown as (two wire) 480 volt feeders for the distribution panels, but not a code violation. Please verify a neutral conductor is not needed. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 06/05/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |