Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM03983
Parcel: 133400020

Address:
555 N PANTANO RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T17CM03983
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet E2; One Line Diagram: Please indicate the new concrete pad thickness and reinforcing at the new transformer.
2. Sheet E2; One Line Diagram: Please verify the new concrete pad at the new SES is designed and provided by TEP.
05/23/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for a complete grounding electrode system for the new service equipment as required per 2011 NEC art. 250.
#2. The new panel feeders leaving the service equipment are shown as 3 wire feeders, then, at the existing panels are shown as 2 wire. Please clarify.
#3. Provide size and structural details for the concrete pad supporting the new service. This information is not provided in the Tucson Electric Power Service Requirement manual.
#4. Provide details or information as to how the existing service equipment will be used as a splice box. Verify it meets the requirements of articles 110.3, 312 and 314 of the NEC. Will the interior bussing or guts be removed? Will the original listings calling it suitable for use as service equipment also allow it to be suitable for a splice box. Please clarify.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC