Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. Justify the cooling capacities of the AC units - the capacity tables for Trane YSC units shows that only AC-4 requires a 5-ton unit.