Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM03894
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03894
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the equipment tags with the mechanical plan, schedule, and the calculations.
2. Justify the cooling capacities of the AC units - the capacity tables for Trane YSC units shows that only AC-4 requires a 5-ton unit.