Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM03894
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the equipment tags with the mechanical plan, schedule, and the calculations. 2. Justify the cooling capacities of the AC units - the capacity tables for Trane YSC units shows that only AC-4 requires a 5-ton unit. |