Permit Number: T17CM03894
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03894
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the equipment tags with the mechanical plan, schedule, and the calculations.
2. Justify the cooling capacities of the AC units - the capacity tables for Trane YSC units shows that only AC-4 requires a 5-ton unit.