Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM03894
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/17/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
05/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations to verify the required capacities of the new AC units. 2. Show that the new AC units comply with the requirements of Section C403, IECC 2012 with respect to efficiency, equipment options (e.g. economizer) and controls. |
05/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/17/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
05/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
05/17/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/17/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/17/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/17/2017 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
05/18/2017 | JVINCEN1 | FIRE | REVIEW | Approved |