Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM03785
Parcel: 10922005L

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T17CM03785
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM03784 thru 03791 – REVISION 3 REVIEW COMMENTS
Reviewer: Chris Anderson, May 9, 2018
BUILDING – COMMERCIAL
Please confirm with the Schneider Structural Engineers that a review from their office is not required for process of this submittal. If a review by Schneider is required, resubmittal drawings must bear their approval stamp.
On stair sections, sheet E1010, the riser heights are incorrectly labeled as 11”. Please revise to 7”.
Guardrails on sheets 301A – 309A show a space from walking surface to bottom rail of 7 ½” and 8 ½”. Per 2012 IBC 1013.4 guards shall not have openings which allow passage of a 4” diameter sphere from walking surface to required guard height.
The guardrail shown on sheet 349A will allow a 4” sphere to pass through between walking surface and bottom rail. See comment 2 above.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2018 SVALENZ1 OUT TO CUSTOMER Completed