Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM03785
Parcel: 10922005L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03785
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM03784, 85, 86, 87, 88, 89, 90, 91, 97 –PLAN REVIEW COMMENTS
3rd REVIEW
Reviewer: Chris Anderson, August 14, 2017
BUILDING – COMMERCIAL
Regarding previous building comment 5, submit an appeal to the Building Official for alternate weep screed design as shown in submittal documents.
08/15/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL - COMMERCIAL
Regarding previous mechanical comment 1, provide a Type II island range exhaust hood in the Community Building per 2012 IMC 507.2.1 and 507.2.2.
08/21/2017 KELLY LEE ZONING REVIEW Reqs Change FROM: Kelly Lee
PDSD Zoning Review Section

PROJECT: T17CM03785
Building Plan Review (3rd Review)
3510 N Craycroft - New Apartment Complex (Multi-Family)

TRANSMITTAL DATE: August 21, 2017


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Previous comment still applies: COMMENT: Zoning has reviewed the building plans for compliance with the development package. While the building footprints are consistent with the current version of the DP under review as it relates to the zoning review purview (Building footprint, height, square footage, site conditions, etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans.
2. COMMENT: Assure that an approved and signed copy of the DP is included in the next submittal of the building plans or remove the DP plan set from the building plan set and reference the DP case number on the Architectural site plan.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plans