Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM03781
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Plan sheet A12 (door hardware schedule) requires security hardware for the holding cell. Please address power requirements and interlock with the fire alarm system if applicable. Ref: 2012 IBC sec. 1008.1.9.10, 2011 NEC. |
| 05/30/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/31/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A01; Building Code Summary: The response letter indicates Sheet A01 has been updated for the code required restrooms. That update was not located. Please verify. 2. Sheet A01: The response letter indicates an exiting plan notation has been added concerning dead ends. No exiting plan was located. Please verify. 3. Sheet A01: The response letter indicates a diagonal distance has been shown on Sheet A12, and has been added to the exiting plan. No diagonal distance is indicated on Sheet A12, nor on the exiting plan. Please verify. |
| 06/02/2017 | KROBLES1 | WWM | REVIEW | Needs Review |