Permit Number: T17CM03781
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03781
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2017 ANDREW CONNOR ZONING REVIEW Approved
05/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/12/2017 CLAYTON TREVILLYAN ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Sheet E1, please include receptacle locations for Break room, Training Room and Restroom.
05/12/2017 LOREN MAKUS ENGINEERING REVIEW Passed
05/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A12; Floor Plan: In the break room (10), an elevation indicates X-X. Please revise.
2. Sheet A12; Interior Wall Types: Is there a W1A wall type on this plan? Please verify.
3. Sheet A13; Interior Elevation B1: Is this elevation indicated on the floor plan? Please verify.
4. Sheet A13; Interior Elevation B1: A section B1/A73 is indicated on the elevation. Please revise.
5. Sheet A13; Section D2: If this is the section indicated on Elevation B1/A13, and this is the break room, the top of the counter must be 34" maximum above finish floor. Please verify.
6. General: Please provide written responses to all review comments.
05/12/2017 ROBERT SHERRY WATER REVIEW Completed
05/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change An indirect waste receptor is not allowed in a restroom. Reference: Section 802.3, IPC 2012.
05/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/30/2017 MMENDIB1 WWM REVIEW Needs Review