Permit Number: T17CM03779
Parcel: 12710084B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03779
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2017 ANDREW CONNOR ZONING REVIEW Approved
05/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that there is an exhaust fan in the existing restroom that moves air at a minmimum of 50 CFM.
2. Provide an exhaust fan for the new restroom the moves at least 100 CFM and operates whenever the AC is delivering air to the room.
05/12/2017 WILDAN ELECTRICAL-COMMERCIAL REVIEW Completed
05/12/2017 LOREN MAKUS ENGINEERING REVIEW Passed
05/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/12/2017 ROBERT SHERRY WATER REVIEW Reqs Change 1. Clarify the location of the activity.
2. Show the location, size, and serial number of the water meter serving this suite.
3. Show the location of the backflow preventer associated with the water meter.
05/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for each restroom lavatory. The faucet shall deliver 0.25 gallons per cycle and each cyccle shall last at least 10-seconds (e.g. a flow rate of 0.5 GPM for 30-seconds delivers 0.25-gallons).
2. Provide a mixing valve listed to ASSE 1070 for the water supply to the lavatories.
05/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/18/2017 GERRY KOZIOL WWM REVIEW Completed