Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM03536
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Original Comment #3: Please provide wall details which include anchoring, bracing and attachment to structure above. Please include type, size and number/spacing of bracing material, anchors and fasteners. Revised detail did not include the type, size or number of fasteners to be used on bracing or attachment to the structure above. 2. Original Comment #9: Sheet A4, Reflected Ceiling Plan. Please provide a detail of the suspended soffit denoted in keynote 5. Include information requested in comment 3. The provided detail did not include information requested in original comment 3. 3. Original Comment #10: Skylight detail was provided. Portions of the skylight detail is cut off and not legible. 4. Original comment #4: Pending appeal to building official. |
| 07/10/2017 | TPROBAS1 | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/10/2017 | TPROBAS1 | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 07/10/2017 | TPROBAS1 | MECHANICAL-COMMERCIAL | REVIEW | Completed |