Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM03513
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2017 | ANDREW CONNOR | ZONING | REVIEW | Passed | |
05/04/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
05/04/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/04/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Passed | |
05/04/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/04/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/04/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the size of the fixture drain for the mop sink; it is 3" on the riser diagram and 2" on the plumbing floor plan. Reference: Section 107.2.1, IBC 2012. 2. The 3" horizontal drain starting at the junction of the fixture drains for the drop sink and the floor sink has no 3" cleanout. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. 3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
05/04/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/05/2017 | JVINCEN1 | FIRE | REVIEW | Approved | |
05/19/2017 | ARUIZ1 | WWM | REVIEW | Needs Review |