Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM03444
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/03/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical design for AC-EX2 as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012. |
05/03/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/03/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/03/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/03/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide justification for using an air break instead of an air gap for the termination of the indirect waste from the ultrasonic cleaner. Reference: Section 802.1, IPC 2012. |
05/04/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Passed | |
05/04/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
05/04/2017 | JVINCEN1 | FIRE | REVIEW | Approved | |
05/18/2017 | MMENDIB1 | WWM | REVIEW | Completed |