Permit Number: T17CM03444
Parcel: 13734001E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03444
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design for AC-EX2 as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
05/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/03/2017 ROBERT SHERRY WATER REVIEW Completed
05/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide justification for using an air break instead of an air gap for the termination of the indirect waste from the ultrasonic cleaner. Reference: Section 802.1, IPC 2012.
05/04/2017 PAUL BAUGHMAN ENGINEERING REVIEW Passed
05/04/2017 ANDREW CONNOR ZONING REVIEW Approved
05/04/2017 JVINCEN1 FIRE REVIEW Approved
05/18/2017 MMENDIB1 WWM REVIEW Completed