Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM03443
Parcel: 123020480

Address:
2734 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03443
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2017 STEVE SHIELDS ZONING REVIEW Needs Review
05/03/2017 LOREN MAKUS ENGINEERING REVIEW Approved
05/04/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please correct the voltages shown on the one-line diagram and the panel schedules.
05/04/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Verify that the installer setup menu for the specified programmable thermostat includes off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
4. Provide information on the sequence of operation for the new restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted (i.e. the exhaust will be running during hours of operation). Reference: Sections 403.2.1 (4) and 403.3, IMC 2012.
5. Provide ventilation calculations per Section 403.3, IMC 2012.
05/04/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a1.0: Please provide a code analysis on this sheet. Include area, occupancy classification, occupant load, construction type, previous use, plumbing fixture requirements, exiting requirements, accessibility requirements, etc.
2. Sheet a2.2; Key notes/General notes: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
3. Sheet a2.2; Floor Plan: Please provide a note for the required accessible counter/sink height in the break room.
4. Sheet a2.2; Floor Plan: Please provide a note for the required accessible reception desk height.
5. Sheet a2.2; Floor Plan: Wall Type 1 was not located on the plan. Please verify.
6. Sheet a2.2; Floor Plan: Are two exits required? The back office exit may not be considered an exit since the office door d107 can be locked. Please verify.
7. Sheet a2.2; Floor Plan: Does the reception door require automatic opener/closer? Please verify.
8. Sheet a6.1; Door Schedule: Are the doors indicated as fire rated wood actually rated doors? Please verify.
9. Sheet a6.1; Door Schedule: Is the safe room door wood construction? Please verify.
10. General: Please provide a detail indicating the interior wall bracing as required by the IBC Section 1607.14. Provide bracing size, spacing, and connection to the top of the partition and to the structure above.
11. General: Please provide written responses to all review comments.
05/04/2017 JVINCEN1 FIRE REVIEW Reqs Change Please provide code analysis section, including occupancy, occupant load, sprinklers, etc.
05/04/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
05/04/2017 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide a ¾" water meter (the records show a 5/8" meter is installed).
2. Show the location and size of the reduced pressure backflow preventer associated with the water meter.
05/04/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/05/2017 ARUIZ1 WWM REVIEW Needs Review