Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T17CM03383
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2017 ANDREW CONNOR ZONING REVIEW Approved COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing a 13' 4" tall attached addition. The proposed side-yard setback is 1' to the East. The required setback would be 8' 10"
05/01/2017 ANDREW CONNOR NPPO REVIEW Passed
10/27/2017 KROBLES1 ENGINEERING REVIEW Needs Review
10/27/2017 KROBLES1 BUILDING-RESIDENTIAL REVIEW Needs Review