Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM03374
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | Sheet G100 lists the specifications for fire sprinklers. Cover sheet indicates no sprinklers.Building requires a sprinkler system per IFC 903.2.1.2 A-2 with an occupant load of 100 or more requires an automatic sprinkler system. Please revise cover sheet. |