Permit Number: T17CM03374
Parcel: 127122650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03374
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2017 MARTIN BROWN FIRE REVIEW Approved Sheet G100 lists the specifications for fire sprinklers. Cover sheet indicates no sprinklers.Building requires a sprinkler system per IFC 903.2.1.2
A-2 with an occupant load of 100 or more requires an automatic sprinkler system. Please revise cover sheet.