Permit Number: T17CM03268
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03268
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 6; Sheets A2.12, A2.22, A2.32, A2.42, and A2.52; General Floor Plan Notes: A reference note has been added to these sheets for the rated assemblies. The second sheet referenced is A5.20, which is not correct. Please correct.
2. Previous Comment 9; Sheet S1.1: The structural calculaitons have been provided, but must bear the seal, signature, date, and expiration date of the license by the design professional on the calculations.
09/21/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/22/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
Also provide a written response.#1. The previous plan review comment concerning the IECC code compliance for lighting energy was not addressed. There was no response found in the plan documents.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2017 QJONES1 APPROVAL SHELF Completed
11/08/2017 QJONES1 OUT TO CUSTOMER Completed
11/08/2017 QJONES1 REJECT SHELF Completed