Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T17CM03207
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2017 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T17CM03207 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. STRUCTURAL PLANS: 1. Show the roof joist size and series for verifying new load carrying capacity, R301.1. 2. Provide a complete braced wall (BW) design, R602.10 include: a. Braced wall panel within 10' of each end and no more than 20' between edges. b. Additional requirements for alternate BW panels with hold-downs, R602.10.6. The living room wall with two doors requires a "qualifying" braced wall panel with hold-downs. SECTIONS - DETAILS: 1. Clarify keynote #7 at the section and elevation plan, sheet 3, R106.1.1. The "3' from exterior walls" needs updating. 2. Provide consistent elevations and details, R106.1.1. Show wooden planks on detail #3/4. 3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value. Notate this requirement on Section "A" sheet 3 and detail #1 sheet 4. ELECTRICAL PLANS: 1. Smoke alarms are required outside each separate sleeping area, R314.3.2. 2. Provide a feeder conductor from the service panel to the new building, E3602.1 & E3603.1. 3. Show 2O AMP small appliance circuits at the kitchen countertop receptacle outlets and Bathroom receptacles, E3703.4. 4. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Show the solar heat gain coefficient SHGC minimum value of 0.25 on sheet 3 , N1102.1. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |