Permit Number: T17CM03153
Parcel: 136129520

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03153
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2017 ANDREW CONNOR ZONING REVIEW Approved
07/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the envelope compliance to indicate that reduced interior lighting has been used to comply with Section C406, IECC 2012. Verify the U-value and SHGC-valuues of the proposed glazing. [Initial comment: Demonstrate energy code compliance for the building envelope (i.e. submit an envelope compliance certificate from COMcheck) using calculations based on the current code - the note on sheet A7.3 appears to reference Chapter 8 of the 2003 IECC. ]Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.]
2. Provide a programmable thermostat the provides the required capabilities. [Initial comment: Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.]
4. Specify the the minimum height of the exhaust discharge ( Section 506.3.13.1, IMC 2012). [Initial comment: Provide details showing how exhaust fans EF-1 and EF-2 and their associated grease ducts are to be installed. Include all required clearance dimensions. Shop drawings are not an acceptable substitute for sealed engineering drawings.] Reference: Sections 506.3.8, 506.3.11, 506.3.13, and 506.5, IMC 2012 and Section 107.2.1, IBC 2012.]
07/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved No comments
07/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show that the proposed use of a 4" 2-way cleanout will not cause damage to the 3" ABS pipe. [Initial comment: Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. The 4" grease waste starting in the kitchen requires a cleanout. Reference: Section 708.7, IPC 2012.]
07/27/2017 ROBERT SHERRY WATER REVIEW Reqs Change The water demand calculations indicate a future demand that will increase the demand beyond the 37.5 GPM that Tucson Water allows for a 1" water meter. [Initial comment: Tucson Water limits 1" water meters to maximum demand of 37.5-GPM. Provide a letter from Tucson Water confirming that the use of a 1" water meter is allowable for this project.]
07/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/29/2017 QJONES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2017 QJONES1 APPROVAL SHELF Completed
08/29/2017 QJONES1 OUT TO CUSTOMER Completed
08/29/2017 QJONES1 REJECT SHELF Completed