Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM03142
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. As per the last plan review it was requested; (a) "Provide a description, voltage, amp, fuse , phase, aic ratings for the service equipment, the AC combiner, PV disconnect". This information could not be found on the plans. (b) "Enlarge the electrical plans to have a minimum text size or font of at least 3/32"min". No Compliance. This is a requirement per City of Tucson Commercial Plan Submittal Requirements. (c) "Provide a written response". Written response could not be located. #2. There are now 2 different sets of plans. One set is a standard set and the other is using the Pima County Model Calculator. One shows a line side tap and the other shows a back fed circuit breaker for the PV interconnection. Please clarify. #3. The registrant seal is not legible. Print is to light. #4. Due to the aptitudes of these comments, additional comments may be generated at the subsequent review. Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. |