Permit Number: T17CM03142
Parcel: 11515051A

Address:
501 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03142
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the last plan review it was requested;
(a) "Provide a description, voltage, amp, fuse , phase, aic ratings for the service equipment, the AC combiner, PV disconnect". This information could not be found on the plans.
(b) "Enlarge the electrical plans to have a minimum text size or font of at least 3/32"min". No Compliance. This is a requirement per City of Tucson Commercial Plan Submittal Requirements.
(c) "Provide a written response". Written response could not be located.
#2. There are now 2 different sets of plans. One set is a standard set and the other is using the Pima County Model Calculator. One shows a line side tap and the other shows a back fed circuit breaker for the PV interconnection. Please clarify.
#3. The registrant seal is not legible. Print is to light.
#4. Due to the aptitudes of these comments, additional comments may be generated at the subsequent review.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements.