Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM03142
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a description, voltage, amp, fuse , phase, aic ratings for the service equipment, the AC combiner, PV disconnect. #2. Indicate conduit, conductor sizes and types between the utility meter and the 12x12 J- Box. #3. Enlarge the electrical plans to have a minimum text size or font of at least 3/32"min. Ref: 2012 IBC 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/11/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |