Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a description, voltage, amp, fuse , phase, aic ratings for the service equipment, the AC combiner, PV disconnect. #2. Indicate conduit, conductor sizes and types between the utility meter and the 12x12 J- Box. #3. Enlarge the electrical plans to have a minimum text size or font of at least 3/32"min. Ref: 2012 IBC 107.2.1, 2011 NEC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/11/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |