Permit Number: T17CM03120
Parcel: 117051360

Address:
450 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM03120
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Delete the remarks for hand sink (17) in the Plumbing Schedule; the hand sink is to be directly connected to the sanitary drain as shown on the plumbing plan. Reference: Section 301.3, IPC 2012.
2. Provide pressure-absorbing devices (ASSE 1010) for the water connections to the glassware washer per the manufacturer's installation instructions. Reference: Sections 303.2 and 604.9, IPC 2012.
3. Verify that the discharge from the glassware washer (kitchen equipment number 15) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.
4. Verify the capacity of the specified water heater. The A.O. Smith model DEL-50 probably has a capacity less than 50 gallons.
07/12/2017 KROBLES1 WWM REVIEW Needs Review