Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM03080
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | A "reference" civil drawing will not substitute for a civil drawing that is to be included as an integral part of the construction documents. Coordinate the civil and plumbing drawings with regard to the locations of the water and sewer services.[Initial comment: Provide the site plan noted on sheet P1.0 that will show the route, slope, and termination of the building sewer as well as the location of the water meter and backflow protector. Reference: Section 107.2.1, IBC 2012.] |
| 06/07/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide the heating and cooling load calculations for the proposed heating and cooling equipment when applying for the permit to install them. [Initial comment: Provide the heating and cooling load calculations used to determine the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] |
| 06/09/2017 | GERRY KOZIOL | WWM | REVIEW | Completed | |
| 06/09/2017 | MMENDIB1 | ZONING | REVIEW | Needs Review | |
| 06/09/2017 | MMENDIB1 | ENGINEERING | REVIEW | Needs Review |