Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM03004
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/18/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Passed | |
| 04/19/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide pressure-absorbing devices for the water connections to appliances equipped with quick acting or solenoid valves (e.g. clothes washers). Reference: Section 604.9, IPC 2012. 2. The minimum font size is 3/32" (see sheet P3.0). Reference Section 107.2.1, IBC 2012. |
| 04/19/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012. 3. Coordinate the HVAC equipment proposed for the server room; a split-system AC unit is scheduled on sheet M2.0 but an exhaust fan is shown on sheet M1.0. Reference Section 107.2.1, IBC 2012. 4. Identify the location of the gravity hood, GH-1. Reference Section 107.2.1, IBC 2012. 5. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted (i.e. the supply air will be exhausted even if the lights are turned off). Reference: Section 403.2.1 (4), IMC 2012. |
| 04/19/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/19/2017 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/19/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 04/19/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/21/2017 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/24/2017 | ARUIZ1 | WWM | REVIEW | Completed |