Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM02890
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/31/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/31/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/31/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The structural detail for support of hood KH-1 shows the hood being horizontally-lagged to a wooden beam which does not comply with the manufacturer's instructions ( "Warning: vertically or horizontally lagging hoods to wooden joists, trusses, or studs is an unacceptable method for hanging hoods. This will lead to both structural and thermal failure causing injury and/or death."). The support of hood KH-2 has not been addressed. [Initial comment: Include the structural details that show how both of the Type I hoods and the new AC units will be supported from the building structure. Verify with the manufacturer that the method of support is appropriate for hood KH-2. Reference: Section 302.1, IMC 2012.] |
05/31/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |