Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM02890
Parcel: 14042075B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM02890
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/31/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/31/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The structural detail for support of hood KH-1 shows the hood being horizontally-lagged to a wooden beam which does not comply with the manufacturer's instructions ( "Warning: vertically or horizontally lagging hoods to wooden joists, trusses, or studs is an unacceptable method for hanging hoods. This will lead to both structural and thermal failure causing injury and/or death."). The support of hood KH-2 has not been addressed. [Initial comment: Include the structural details that show how both of the Type I hoods and the new AC units will be supported from the building structure. Verify with the manufacturer that the method of support is appropriate for hood KH-2. Reference: Section 302.1, IMC 2012.]
05/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved