Permit Number: T17CM02890
Parcel: 14042075B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02890
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
04/14/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/14/2017 ROBERT SHERRY WATER REVIEW Completed
04/14/2017 JVINCEN1 FIRE REVIEW Approved
04/17/2017 ANDREW CONNOR ZONING REVIEW Approved
04/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Identify the exterior lighting on the floorplan and luminaire schedule, and provide compliance with the Tucson/Pima County Outdoor Lighting Code.
#2. Identify all the interior luminaire types on the floorplans and luminaire schedule. Provide compliance with the 2012 IECC for lighting.
#3. Identify the Neon Lighting shown on Panel A on the floorplans and luminaire schedule.
Ref: 2012 IBC 107.2.1, 2011 NEC
04/17/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
04/17/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/18/2017 MMENDIB1 WWM REVIEW Needs Review