Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM02887
Parcel: 117110170

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02887
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2017 PATRICIA GEHLEN ZONING REVIEW Approved
04/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an auxiliary or secondary condensate drain system for AC 5.1. Reference: Section 307.2.3, IMC 2012.
2. Clarify the reason for undercutting the door to the mailroom. Reference: Section 601.2, IMC 2012.
04/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. The specified backflow prevention device for each coffee maker is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012.
04/14/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/14/2017 ROBERT SHERRY WATER REVIEW Completed
04/17/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/17/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/25/2017 ARUIZ1 FIRE REVIEW Needs Review Fire code administrator currently researchinig bldg.
04/25/2017 ARUIZ1 WWM REVIEW Completed