Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02887
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/14/2017 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
04/14/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an auxiliary or secondary condensate drain system for AC 5.1. Reference: Section 307.2.3, IMC 2012. 2. Clarify the reason for undercutting the door to the mailroom. Reference: Section 601.2, IMC 2012. |
04/14/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. The specified backflow prevention device for each coffee maker is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012. |
04/14/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
04/14/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/17/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/25/2017 | ARUIZ1 | FIRE | REVIEW | Needs Review | Fire code administrator currently researchinig bldg. |
04/25/2017 | ARUIZ1 | WWM | REVIEW | Completed |