Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM02827
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2017 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 04/27/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: Oregano's Pizza Bistro @ Irvington & I-19 Commercial Center T17CM02827 Building Plan (1st Review) TRANSMITTAL DATE: April 27, 2017 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. As there are significant changes proposed to the site development package DP16-0044 will need to be revised prior to approval of the building plans. 3. If development package sheets are going to be provided in the building plan set the development package sheets need to be the signed approved sheets. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/02/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Cover Sheet; Codes Used: Please add the 2009 ICC/ANSI A117.1 accessibility code. 2. Sheets A1.0, A1.1, A1.1.1, and A1.2 (Plans); Sheet A2.0 (Plan): Please coordinate the north arrow indication on these sheets. 3. Sheet A5.0; Typical ADA Dimensions: Please add a detail on this sheet for the horizontal grab bar on the back wall per the ICC/ANSI Figure 609.4.2. 4. Sheet A7.0; Details 2, 3, and 5: The wall ties spacing is indicated as 116". Please revise. 5. Sheet A9.0: This sheet indicates A9.1 in the title. Please revise. 6. Sheet S2.1 (Foundation Notes); Sheet S2.2 (Roof Framing Notes): The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 7. Sheets S3.1, S3.2, S4.1, and S4.2: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 8. Sheet S4.2; Detail 223: Notes 5, 6, and 7 are misidentified. Please verify. 9. Sheet S4.2; Detail 237: Note 10 is indicated on the detail, but not included in the notes. Please verify. 10. Structural Calculations: The Basis for Design indicated in the calculations does not match the information provided on Sheet S1.1 (Concrete). Please verify. 11. Structural Calculations: The evaluation reports ICBO 2388 and 1372 referenced in the shear wall detail are no longer valid. Please revise. 12. General: Please provide written responses to all review comments. |
| 05/02/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the specification for the lavatory faucets to include a mixing valve listed to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 2. At a minimum, beverage dispensers require the use of a backflow preventer listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012. 3. Verify that the discharge from the glass washer and the dish machine (kitchen equipment numbers 021 and 103) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012. 4. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. 5. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater (e.g. most new fryers) will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2012. |
| 05/03/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | . |
| 05/05/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the building envelope (e.g. COMcheck); use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-values of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. The U-values and SHGC for the fenestration components shall be NFRC-certified. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 2. Show how the requirements of Section C406, IECC 2012 are to be satisfied. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 4. Verify that the installer setup menu for the specified programmable thermostat includes an automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy). Reference: Section C403.2.4, IECC 2012. 5. Clarify how excess outside air relief from the building is to be accomplished without recirculation of the relief air. Reference: Section C403.3.1.1.4, IECC 2012. |
| 05/09/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | Site plan layout must match approved DP layout. |
| 05/11/2017 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/11/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Plan Sheet E2.0. All existing exterior lighting must be included in the lumen calcs if located on this parcel or property. (See note under Lumens Per Acre Calculation). Per section 102, 104, and 401, TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. #2. Indicate on the plans the lamp color temperature output for all exterior luminaires. Ref: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/01/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |