Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM02821
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2017 | TPROBAS1 | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/25/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/25/2017 | TPROBAS1 | WATER | REVIEW | Completed |