Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02664
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/06/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
04/06/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
04/06/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/06/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/13/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/13/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/13/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the reason for using an occupant density substantially lower than shown in Table 403.3, IMC 2012. Reference: Sections 403.2 and 403.3, IMC 2012. 2. Provide heating and cooling load calculations to justify the total capacity of the HVAC units serving the theater. Reference: Section C403.2.1, IECC 2012. |