Permit Number: T17CM02664
Parcel: 12217278D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02664
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2017 ANDREW CONNOR ZONING REVIEW Approved
04/06/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/06/2017 MARTIN BROWN FIRE REVIEW Approved
04/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/13/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/13/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the reason for using an occupant density substantially lower than shown in Table 403.3, IMC 2012. Reference: Sections 403.2 and 403.3, IMC 2012.
2. Provide heating and cooling load calculations to justify the total capacity of the HVAC units serving the theater. Reference: Section C403.2.1, IECC 2012.