Permit Number: T17CM02641
Parcel: 103090670

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T17CM02641
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2017 ANDREW CONNOR ZONING REVIEW Approved
04/05/2017 LOREN MAKUS ENGINEERING REVIEW Approved
04/10/2017 ENEWCOM1 ADA REVIEW Passed
04/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.0; Scope of Work: The note indicates this is a revision to approved plans. Please revise that sentence to a tenant imrprovement to an existing space (leave the remainder of the note as is).
2. Sheet A0.0; Code information: Please finish the 'age of building' note.
3. Sheet A0.0; Code information: Please add the 2009 ICC/ANSI A117.1 accessibility code to this list.
4. Sheet A1.0; Partition legend: Please remove the partition types that are not indicated on this plan.
5. Sheet A2.0; Key notes: Note 15 is not indicated on this plan (note 5 on the west wall is incorrect). Please verify.
6. Sheet A2.0; Partition legend: Please remove the partition types that are not indicated on this plan.
7. Sheet A2.0; Partition legend: For the partitions that are used on this project, please add a reference to each, indicating the pertinent detail 1, 2, 3, 4, or 7 on sheet A3.0.
8. General: Please provide written responses to all review comments.
04/10/2017 LBOJORQ1 WWM REVIEW Approved
04/10/2017 LBOJORQ1 FIRE REVIEW Needs Review
04/10/2017 LBOJORQ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review