Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02595
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/28/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/28/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the modifications to the building envelope comply with the requirements of the current energy conservation code. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration and doors on the architectural drawings. Reference: Sections C101.4.3, C103.2, and C303.1.3, IECC 2012. |
| 05/04/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Keynotes: Note 24 indicates an existing fire rated wall. Please provide the fire resistance rating for that wall. 2. Sheet A1.0; Keynotes: Note 14 references a new interior exit stairway. An enclosure will be required around this stair complying with the IBC Section 707. Please reference the IBC Section 1022. 3. Sheet A1.0; Floor Plan: The new interior exit stairway shall terminate at an exit discharge or public way, or be provided with an exit passageway constructed in accordance the the IBC Sections 707 and/or 711. Please reference the IBC Sections 1022.3 and 1022.3.1. 4. Sheet A1.0; Keynotes: Note 17 indicates a new steel stud partition. Please provide the construction of the wall (stud size, spacing, stud gauge, bracing, etc.), using notes or details on the drawings as required. 5. Sheet A1.0; Keynotes: Note 20 references IBC Sections 1007.2.1 and 1007.4 as related to an existing roof top generator (on an adjacent tenant space). Please clarify on the drawings the note as it relates to the elevators. 6. Sheet A1.0; Keynotes: Note 24 indicates a new steel stud wall. Please provide the construction of the wall (stud size, spacing, stud gauge, bracing, etc.), using notes or details on the drawings as required. 7. Sheet A2.0; Keynotes: Note 13 indicates an existing fire rated wall. Please provide the fire resistance rating for that wall. 8. Sheet A2.0; Keynotes: Note 8 indicates the infill of an existing exit door from an adjacent tenant space. Please verify on the drawings this will not prohibit the existing required egress into that stair from the adjacent space. 9. Sheet A2.0; Keynotes: Note 13 indicates a new steel stud wall. Please provide the construction of the wall (stud size, spacing, stud gauge, bracing, etc.), using notes or details on the drawings as required. 10. Sheet A2.0; Keynotes: Note 6 references an enlarged restroom plan. Where is that plan located? 11. Sheet A2.0; Keynotes: Note 9 was not located on these plans. Please verify. 12. Sheet A5.0; Keynotes: Note 13 indicates a new aluminum canopy in two locations. Please provide stamped calculations and drawings for these canopies. 13. General; Comments 2 and 3: These comments were provided on this review to assist in planning for the tenant improvement for this space. No action is required at this time. 14. General: Please provide written responses to all review comments. |
| 05/08/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/08/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Plan Sheets E4.0, E5.0. Keynotes are missing on the floor plans. #2. Plan Sheet E5.0 is missing Engineer Stamp. Ref: 2012 IBC sec. 107.2.1 |