Permit Number: T17CM02549
Parcel: 128100530

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T17CM02549
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/04/2017 ENEWCOM1 ADA REVIEW Passed
04/04/2017 ROBERT SHERRY WATER REVIEW Completed
04/04/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. PLEASE SHOW THE FULL PANEL DESIGNATION FOR THE BRANCH CIRCUITING ON THE POWER AND LIGHTING PLANS.
#2. PROVIDE FULL COMPLIANCE WITH THE 2012 IECC LIGHTING.
REF: 2012 IBC 107.2.1, 2011 NEC ART. 408.4
04/04/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS A050 AND A051; PATH OF TRAVEL PLANS: THE ELEVATIONS, BUILDING SECTIONS, AND BUILDING DETAILS REFERENCE SHEET THAT WERE NOT LOCATED IN THE SUBMITTAL DRAWINGS. PLEASE CLARIFY.
04/04/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/04/2017 LOREN MAKUS ENGINEERING REVIEW Approved
04/04/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Protect water supply connections to beverage dispensers with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
04/05/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change 1.The proposed floor plan eliminates the access to the second stairwell. Table 1021.2(2) does not allow one exit from this space because it is above the second story.

2. Section 1015.2.1 requires that when two exits are required that they are separated by not less than one-third of the length of the maximum overall diagonal dimension of the area served.

Please revise the exit configuration for this tenant space.
04/11/2017 GERRY KOZIOL WWM REVIEW Completed
04/11/2017 ANDREW CONNOR ZONING REVIEW Completed