Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T17CM02549
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/04/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
04/04/2017 | ENEWCOM1 | ADA | REVIEW | Passed | |
04/04/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/04/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. PLEASE SHOW THE FULL PANEL DESIGNATION FOR THE BRANCH CIRCUITING ON THE POWER AND LIGHTING PLANS. #2. PROVIDE FULL COMPLIANCE WITH THE 2012 IECC LIGHTING. REF: 2012 IBC 107.2.1, 2011 NEC ART. 408.4 |
04/04/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS A050 AND A051; PATH OF TRAVEL PLANS: THE ELEVATIONS, BUILDING SECTIONS, AND BUILDING DETAILS REFERENCE SHEET THAT WERE NOT LOCATED IN THE SUBMITTAL DRAWINGS. PLEASE CLARIFY. |
04/04/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/04/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/04/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Protect water supply connections to beverage dispensers with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. |
04/05/2017 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1.The proposed floor plan eliminates the access to the second stairwell. Table 1021.2(2) does not allow one exit from this space because it is above the second story. 2. Section 1015.2.1 requires that when two exits are required that they are separated by not less than one-third of the length of the maximum overall diagonal dimension of the area served. Please revise the exit configuration for this tenant space. |
04/11/2017 | GERRY KOZIOL | WWM | REVIEW | Completed | |
04/11/2017 | ANDREW CONNOR | ZONING | REVIEW | Completed |