Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM02533
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/10/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | T17CM02521/2517/2530/2533 –PLAN REVIEW COMMENTS MECHANICAL - COMMERCIAL Reviewer: Chris Anderson, May 8, 2017 The HVAC load calculations provided on sheet M0.2 in response to previous mechanical comment 2 appear to indicate that heating and cooling units selected for buildings 1-4 are oversized. By calculation, the schedule for Building 1 shows a cooling capacity 11.36 MBH in excess of the calculated cooling load, Building 2 shows a cooling capacity 39.02 MBH in excess of the load, Building 3 shows a cooling capacity 212.78 MBH in excess of the load, and Building 4 shows a cooling capacity 17.60 MBH in excess of the load. Per 2012 IECC C403.2.2, the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C403.2.1. The capacity excesses are substantial, particularly for buildings 2 and 3. Please show specifically how your selections for each building are in compliance with this Code section. |
| 05/18/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/22/2017 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/22/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | DP must be approved |