Permit Number: T17CM02533
Parcel: 13815014G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02533
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2017 MARTIN BROWN FIRE REVIEW Needs Review
04/21/2017 ROBERT SHERRY WATER REVIEW Needs Review
04/21/2017 LOREN MAKUS ENGINEERING REVIEW Needs Review DP must be approved first.
04/25/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM02533 –PLAN REVIEW COMMENTS (BUILDING 4)
BUILDING – COMMERCIAL
Reviewer: Chris Anderson, April 25, 2017

On Enlarged Bldg #4 Teachers Lounge plan 11/A5.0 a sink is located in a 36” base cabinet abutting the refrigerator which extends past the front of the sink countertop. Per ICC/ANSI A117.1-2009 606.2, exception 1, a parallel approach to the sink is acceptable if centerline of the sink is centered on the required 48” wheelchair floor space (Fig. 305.3). The refrigerator prevents compliance.
04/25/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
04/25/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Approved
04/25/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL - COMMERCIAL
Reviewer: Chris Anderson, April 25, 2017

On the split system and mini split equipment schedules – Building 4, sheet M5.1, the cooling ambient air dry bulb is shown as 107-degrees F summer design temperature. Per City of Tucson amendment to the 2012 IECC, the summer Db design temperature must be 104-degrees F. Revise schedules and reselect heating and cooling unit if needed to comply.
Provide heating and cooling load calculations summary sheets to justify the capacity of selected equipment. Ref. 2012 IECC C403.2.1 and C403.2.2. Use 104-degrees F summer DB outdoor design temperature with 66-degrees F design wet bulb temperature, and 32-degrees F winter DB outside design temperature per City of Tucson amendment to the 2012 IECC. Per IECC C403.2.1 and C403.2.2 “the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C403.2.1.”
04/28/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
04/28/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:

Need civil drawing showing location of connection to the existing on-site private sewer and need to show location, size and serial number of all water meters on the property.

PCRWRD & COT Water indicate only one existing 1-1/2” water meter #13738862 on this property. (user fees since 2008).

Do buildings #1, #2 and #3 all connecting to this existing 1-1/2” water meter?



*Drawing P3.1 indicates a new 1-1/2” water meter for new building #4. Fee: $27,030.00.



Need to clarify building numbers on drawings. Some do not match.

*In particular buildings #3 & #4

Need Type III Capacity from Kurt Stemm – 520-724-6607.