04/05/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. PROVIDE FOR TAMPER RESISTANT RECEPTACLES AS REQUIRED PER NEC ART'S. 210.52, 210.60 ( DORMITORIES) 406.12, 406.13.
#2. THE ONE LINE DIAGRAM SHOWS PANELS HAVING MAIN CIRCUIT BREAKERS, BUT THE PANEL SCHEDULES SHOW MAIN LUG.
#3. THE VOLTAGE RATINGS OF THE MSB DO NOT CORRELATE WITH THE PANELS DOWN STREAM.
REF: 2012 IBC SEC. 107.2.1, 2011 NEC.