Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM02529
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. PROVIDE FOR TAMPER RESISTANT RECEPTACLES AS REQUIRED PER NEC ART'S. 210.52, 210.60 ( DORMITORIES) 406.12, 406.13. #2. THE ONE LINE DIAGRAM SHOWS PANELS HAVING MAIN CIRCUIT BREAKERS, BUT THE PANEL SCHEDULES SHOW MAIN LUG. #3. THE VOLTAGE RATINGS OF THE MSB DO NOT CORRELATE WITH THE PANELS DOWN STREAM. REF: 2012 IBC SEC. 107.2.1, 2011 NEC. |
| 04/05/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/13/2017 | LBOJORQ1 | OUT TO CUSTOMER | Completed |