Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM02529
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02529
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. PROVIDE FOR TAMPER RESISTANT RECEPTACLES AS REQUIRED PER NEC ART'S. 210.52, 210.60 ( DORMITORIES) 406.12, 406.13.
#2. THE ONE LINE DIAGRAM SHOWS PANELS HAVING MAIN CIRCUIT BREAKERS, BUT THE PANEL SCHEDULES SHOW MAIN LUG.
#3. THE VOLTAGE RATINGS OF THE MSB DO NOT CORRELATE WITH THE PANELS DOWN STREAM.
REF: 2012 IBC SEC. 107.2.1, 2011 NEC.
04/05/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2017 LBOJORQ1 OUT TO CUSTOMER Completed