Permit Number: T17CM02522
Parcel: 10409002D

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02522
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the cooling load calculations to address the rooms being conditioned. There are no windows in the room and, other than the internal loads, the proposed unit is only used to reduce the room temperature from 76 to 64 degrees Fahrenheit. [Initial comment: Provide heating and cooling load calculations that justify the capacities of AC-1, AC-2, AC-3, and AC-4. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.]
05/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the 8" steel studs are connected to the surrounding walls. Coordinate the support design with the specification for the water heater (i.e. "Provide manufactured adjustable wall mount"). [Initial comment: Provide a design for the support of the proposed water heater. Reference: Section 301.2, IPC 2012.]