Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM02522
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/11/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the cooling load calculations to address the rooms being conditioned. There are no windows in the room and, other than the internal loads, the proposed unit is only used to reduce the room temperature from 76 to 64 degrees Fahrenheit. [Initial comment: Provide heating and cooling load calculations that justify the capacities of AC-1, AC-2, AC-3, and AC-4. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] |
| 05/11/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the 8" steel studs are connected to the surrounding walls. Coordinate the support design with the specification for the water heater (i.e. "Provide manufactured adjustable wall mount"). [Initial comment: Provide a design for the support of the proposed water heater. Reference: Section 301.2, IPC 2012.] |