Permit Number: T17CM02521
Parcel: 13815014G

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02521
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved
05/09/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
05/09/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Approved
05/09/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change T17CM02521/2517/2530/2533 –PLAN REVIEW COMMENTS
MECHANICAL - COMMERCIAL
Reviewer: Chris Anderson, May 8, 2017

The HVAC load calculations provided on sheet M0.2 in response to previous mechanical comment 2 appear to indicate that heating and cooling units selected for buildings 1-4 are oversized. By calculation, the schedule for Building 1 shows a cooling capacity 11.36 MBH in excess of the calculated cooling load, Building 2 shows a cooling capacity 39.02 MBH in excess of the load, Building 3 shows a cooling capacity 212.78 MBH in excess of the load, and Building 4 shows a cooling capacity 17.60 MBH in excess of the load. Per 2012 IECC C403.2.2, the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C403.2.1. The capacity excesses are substantial, particularly for buildings 2 and 3. Please show specifically how your selections for each building are in compliance with this Code section.
05/17/2017 LOREN MAKUS ENGINEERING REVIEW Approved
05/18/2017 MARTIN BROWN FIRE REVIEW Approved
05/22/2017 GERRY KOZIOL WWM REVIEW Approved