Permit Number: T17CM02517
Parcel: 13815014G

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM02517
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please revise the OCPD and conductor sizes load calcs for the Insta Hot. 4100 KW x 208volts @ 125% = 25amps.
2011 NEC 422.10
10/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed