Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please revise the OCPD and conductor sizes load calcs for the Insta Hot. 4100 KW x 208volts @ 125% = 25amps. 2011 NEC 422.10 |
10/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |