Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2017 ANDREW CONNOR ZONING REVIEW Approved
03/29/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
03/29/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/29/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/29/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; FLOOR PLAN: FOR A B OCCUPANCY WITH MORE THAN 15 OCCUPANTS, TWO RESTROOMS ARE REQUIRED PER THE IBC TABLE 2902.1. PLEASE REVISE.
2. SHEET A2.0; ENLARGED PLAN 5: PLEASE INCLUDE ELEVATIONS FOR THE GRAB BAR LOCATIONS PER THE ICC/ANSI FIGURES 604.5.1 AND 604.5.2 ON THIS SHEET (NOTED ON THIS PLAN).
3. SHEET A3.0; DETAIL 1: PLEASE INCLUDE THE BRACE SIZE, OR REFERENCE METAL WALL STUD.
4. SHEET A3.0; DETAIL 2: PLEASE INDICATE THE BOLT SIZE THAT CONNECTS THE HOT WATER HEATER FRAME TO THE WALL ('ANCHOR TO WALL IN APPROVED MANNER' IS NOT ACCEPTABLE.
5. SHEET A3.0; DETAIL 2: PLEASE INDICATE THERE ARE TWO OF THE ANGLE FRAMES AT THE HOT WATER HEATER.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/29/2017 ROBERT SHERRY WATER REVIEW Completed
03/29/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
03/29/2017 ANY FIRE REVIEW Active
03/29/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/29/2017 ANY WWM REVIEW Active