Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM02430
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/19/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. No reference copy of the civil and plumbing drawings for the building shell was included with this submittal. [Initial comment: Provide a reference copy of the civil and plumbing drawings for the building shell. Reference: Section 107.2.1, IBC 2012.] 2. General note F on sheet P-2000 does not clearly state that all directly connected beverage dispensers are required to have backflow preventers listed to ASSE 1022 (e.g. Watts model 9D is listed to ASSE 1012). See also sheet P-1000 which incorrectly calls for Watts model 9D backflow preventers to be installed for beverage dispensers. [Initial comment: Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.] |
| 05/19/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/25/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |