Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2017 STEVE SHIELDS ZONING REVIEW Approved
05/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. No reference copy of the civil and plumbing drawings for the building shell was included with this submittal. [Initial comment: Provide a reference copy of the civil and plumbing drawings for the building shell. Reference: Section 107.2.1, IBC 2012.]
2. General note F on sheet P-2000 does not clearly state that all directly connected beverage dispensers are required to have backflow preventers listed to ASSE 1022 (e.g. Watts model 9D is listed to ASSE 1012). See also sheet P-1000 which incorrectly calls for Watts model 9D backflow preventers to be installed for beverage dispensers. [Initial comment: Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.]
05/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/25/2017 LOREN MAKUS ENGINEERING REVIEW Passed