Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM02430
Parcel: 138244020

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02430
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2017 MARTIN BROWN FIRE REVIEW Approved
04/05/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a reference copy of the civil and plumbing drawings for the building shell. Reference: Section 107.2.1, IBC 2012.
2. Provide an automatic faucet for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the metering cycle will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the thermostatic valves for the restroom lavatories (keynote 5, P-2000) are listed to ASSE 1070. Reference: Section 607.1.2, IPC 2012.
4. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
5. Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
6. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
7. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
8. The use of an island vent (detail 05/P-5000) is restricted to sinks and lavatories; floor sinks are not be drained using an island vent system. Reference: Section 916.1, IPC 2012.
9. A dishwasher is required to discharge through a gravity grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
10. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
11. Floor sinks, rinse sinks, and prep sinks are required to be connected to a grease interceptor. Reference: section 1003.3, IPC 2012 as amended by the City of Tucson.
04/05/2017 ROBERT SHERRY WATER REVIEW Completed
04/10/2017 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Requires approval of the latest revision for DP15-0037 prior to approval of combo permit.
04/10/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM02430 - (Reference DP16-0183)
Building Plan Review (1st Review)
1765 W Valencia Road - Food Service Use (Starbucks)

TRANSMITTAL DATE: April 10, 2017

DUE DATE: April 24, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the Approved development package DP16-0183. While the building footprint is consistent with the approved DP as it relates the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans.


2. COMMENT: Label the building heights on the building elevations sheet A-2001 and A-2002. The overall building heights based on all walls proposed, and specifically the height to the highest part of the roof. See redlines on sheet A-2001.


3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: revised elevations drawings with height dimensions
04/18/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. convection ovens). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
04/21/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/01/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved